SPECIFICATIONS - CURRENT DETECTION PART
Sensoring MethodFlexible Split-Core Type
Inside Diameterφ210mm (total length approx. 650mm)
Influence of Residual CurrentLess than 0.25A (at AC 50A, the point where influence is most receivable)
Withstanding VoltageAC 2200V/1 minute
Length of Lead WireApprox. 2m between CT and Measuring Part
SPECIFICATIONS - MEASURING PART
Measuring FunctionAC Line Current, AC Leakage Current
Measuring MethodDual Integration Mode
Measuring RangeAC 1000mA/10A/100A/1000A (50/60 Hz)
Range Selection4 Range Manual by Rotary Switch
Sampling Rate2 Times/sec.
DisplayLCD max. 9999 reading with annunciators
Over Range Indication"OL" mark on LCD
Data Hold Indication"DH" mark on LCD
Low Battery Indication"B" mark on LCD
Data Hold Functionby "DH" Switch
Filter Functionby Filter Switch to cut hi-frequency (Low Pass Filter for cut off 150 Hz)
Backlight FunctionBy pressing this switch, back light appears on LCD display and will get off by pressing this switch once again.
Signal OutputDC 100mV full scale to each range (Output impedance : less than 10KΩ)
Auto Power OffApprox. 10 minutes after power on (this function is cancelled in case of using recorder cable for signal output)
SPECIFICATIONS - GENERAL SPECIFICATION
Circuit VoltageLess than AC 600V
Operating Temperature0~40℃, < 80%RH without condensation
Storage Temperature-10~60℃, < 70%RH without condensation
Withstanding VoltageAC 2200V/1 minute
Power Supply1.5V (“AA” size, UM-3) x 6
Dimension (Measuring Part)159(W)×105(H)×53(D) mm
Standard accessoriesBattery (UM-3 x 6), Instruction Manual , Carrying Case
SPECIFICATIONS - ACCURACY
Accuracy23℃±5℃, less than 80%RH
±3%rdg±5dgt (1000mA)
±2.5%rdg±5dgt (10A/100A/1000A)
Signal Output ±2% F.S.
Resolution0.1mA (1000mA)
0.001A (10A)
0.01A (100A)
0.1A (1000A)